NFPA 80 Considers Annex Note to Clear Up Framing Confusion

Date: 14 April 2014

The misinterpretation of IBC model building codes and NFPA 80 and 101 guidelines regarding where fire resistive-rated glazing versus fire protective-rated glazing must be used can have costly results.

The critical concern here pertains to the protection against the transmission of radiant heat.  Fire-resistive glass and frame assemblies provide a radiant heat barrier that ensures the safe evacuation of the building, protects fire-fighters while they do their job, and reduces the loss suffered by building owners.  Since the codes can lead to confusion which often results in the use of insufficiently safe framing assemblies, a proposed NFPA 80 annex note that clarifies situations where fire-resistive framing must be used recently passed the first NFPA 80 Technical Committee ballot.Simply put, the annex note seeks to underscore that the entire assembly must fully meet the requirements of the code.When codes require fire resistive glazing, the entire framing assembly must meet the same fire resistive requirement.   Combining non-fire resistive framing products, such as standard hollow metal framing, with fire-resistive glazing downgrades the entire assembly, resulting in an insufficiently safe assembly and a failure to meet the true intent of the building code. Examples abound where the authority having jurisdiction (AHJ) has ordered the removal of non-compliant assemblies.           

When Hollow Metal Framing May Not Be Used

Framing systems such as hollow metal are often tested in accordance with the NFPA 252 and NFPA 257 test standards up to durations typically required for fire-resistive assembles meeting ASTM E-119. However, there are situations where such framing systems should not be used despite their demonstrated ability to meet the required duration of the fire rating. The proposed NFPA 80 annex note offers guidance about Sections 6.3.3.3 and 6.3.3.4 and explains where fire resistive framing tested to ASTM E-119 should be used to limit temperature rise and block radiant heat (see proposed annex text revision here)

 

Fire Resistive Framing with Fire Resistive Glazing



  • Sidelites/transom frames in 60- minute or 90-minute fire door assemblies. Where NFPA 101 and IBC 2012 require the use of 60-minute or 90-minute fire doors, hollow metal sidelite/transom frames tested only to NFPA 252 are not permitted.  In a door assembly required to be rated 60 or 90 minutes, while the door and door frame may be rated 60 or 90 minutes in accordance with NFPA 252, the sidelite/transom portion of the assembly should also be tested to ASTM E-119 or UL 263. NFPA 101 and IBC 2012 require sidelites/transom portions of the assembly to be rated equal to the wall. Click here for the NFPA 101 fire rated glazing assemblies tables. Click here for the IBC 2012 fire rated glazing assemblies tables.

  • Sidelites/transom frames in 1 and 2 hour stairwells enclosures in sprinklered buildings. While 60-90 minute temperature rise doors in 1 and 2 hour stairwells in fully sprinklered buildings may not have to meet temperature rise requirements under the IBC model building code, the sidelite/transom frames and glazing must be a fire resistive assembly (i.e., must meet ASTM E-119.) Fire-protective framing systems tested up to 90 minutes are not allowed.

  • Assemblies that exceed 25% of the wall. When sidelites/transom frames exceed 25% of a wall adjoining a partitioned space, the assemblies must meet ASTM E-119 testing requirements and must be rated equal to the wall in which they are installed. Again, framing systems such as standard hollow metal cannot be used.


The glazing used in this 1-hour exit corridor exceeds 25% of the wall area. As a result, 60-minute fire resistive glazing and framing tested to ASTM E-119 was used in the assembly adjacent to the door.

Proposed NFPA 80 Annex Note Would Help Avoid Costly Mistakes

In November 2013, Kate Steel, a nationally recognized code consultant and NFPA 80 task group member, presented examples of improper installations of fire-rated products that were later ordered removed. These examples helped persuade the NFPA 80 Technical Committee to finalize language of a proposed annex note. "This is a positive contribution by the NFPA 80 Technical Committee to explain requirements that are often misunderstood by both design professionals and code officials," said Steel. "I spend considerable time answering framing requirement questions — unfortunately, sometimes after an improper installation has taken place. We really need to clear up confusion about framing. The proposed annex will help code users better understand the complexities of the code provisions." Hopefully Kate's advocacy, and that of members on the NFPA 80 Technical Committee, for the utmost fire protection whenever and wherever possible will lead to a clearer understanding on the part of specifiers, designers, and contractors regarding the safe use of fire-rated glazing systems.

600450 NFPA 80 Considers Annex Note to Clear Up Framing Confusion glassonweb.com

See more news about:

Others also read

"Opportunity in the Indian Glass Market - 2014 : Market size, Market share, Market landscape, Market trend analysis, Growth drivers, Future opportunity, Future forecast" provides an insight into the Indian Glass current market scenario, structure and practices.
Dubai Investments (DI) CEO Khalid Bin Kalban has revealed that the Company seeks to examine several expansion opportunities in 2015.
This report was created for strategic planners, international executives and import/export managers who are concerned with the market for nonwired glass sheets of float glass and surface ground or polished glass.
New Business to Support Company's Growing Presence in East and Central African Markets - H.B. Fuller Company (NYSE: FUL) announced today that it has signed an agreement to purchase Continental Products Limited, a provider of industrial adhesives in East and Central Africa.
Coinciding with the fulfillment of the ARTESUN project´s first year (November), the third Project Meeting took place at Corning headquarters in Avon, France    Funded by the European Comission through its Seventh Framework Programme, ARTESUN Project aims to develop organic photovoltaic solar cells (OPV) through the implementation of three full-scale prototypes.
Dear Valued Shareholders, it’s been a breakthrough, banner year for New Energy Technologies. I’m proud to share many of our 2013 – 2014 accomplishments and development goals planned for the year ahead.

Add new comment